Main conducting paths
Rated operating voltage [Ue]
200 – 480 V AC
Supply frequency [fLN]
50/60 Hz
Rated operational current [Ie ]AC-53 [Ie]
41 A
Assigned motor rating (Standard connection, In-Line)at 230 V, 50 Hz [P]
11 kW
Assigned motor rating (Standard connection, In-Line)at 400 V, 50 Hz [P]
22 kW
Assigned motor rating (Standard connection, In-Line)at 200 V, 60 Hz [P]
10 HP
Assigned motor rating (Standard connection, In-Line)at 230 V, 60 Hz [P]
15 HP
Assigned motor rating (Standard connection, In-Line)at 460 V, 60 Hz [P]
30 HP
Overload cycle to IEC/EN 60947-4-2AC-53a
41 A: AC-53a: 3 – 5: 75 – 10
Overload cycle to IEC/EN 60947-4-2Internal bypass contacts
✓
Short-circuit ratingType “1” coordination
NZMN1-M50/PKZM4-49
Short-circuit ratingType „2“ coordination (additional with the fuses for coordination type „1“)
3 x 170M3013
Fuse base (number x part no.)
3 x 170H3004
Terminal capacities
Cable lengthsSolid
1 x (25 – 70)
2 x (6 – 25) mm2
2 x (6 – 25) mm2
Cable lengthsStranded
1 x (25 – 70)
2 x (6 – 25) mm2
2 x (6 – 25) mm2
Cable lengthsSolid or stranded
1 x (12 – 2/0) AWG
Cable lengthsCopper band
2 x 9 x 0.89 x 9 x 0.8 MM
Cable lengthsTightening torque
6 (≤ 10 mm²); 9 (> 10 mm²) Nm
Cable lengthsScrewdriver (PZ: Pozidriv)
PZ2; 1 x 6 mm mm
Control cablesSolid
1 x (0.5 – 2.5)
2 x (0.5 – 1.0) mm2
2 x (0.5 – 1.0) mm2
Control cablesFlexible with ferrule
1 x (0.5 – 1.5)
2 x (0.5 – 0.75) mm2
2 x (0.5 – 0.75) mm2
Control cablesStranded
1 x (0.5 – 1.5)
2 x (0.5 – 1.0) mm2
2 x (0.5 – 1.0) mm2
Control cablesSolid or stranded
1 x (21 – 14)
2 x (21 – 18) AWG
2 x (21 – 18) AWG
Control cablesTightening torque
0.4 Nm
Control cablesScrewdriver
0,6 x 3,5 mm